Battery Runtime and Charging Time
Last updated: · 2 min read
How long a battery lasts depends on capacity, depth of discharge and inverter efficiency. The tool gives the runtime, the time to recharge what was used, the discharge current and the charge rate (C). This guide explains the formula, works through an example and lists the usual mistakes.
Formula
Energy = Ah × V × DoD Runtime = energy × inverter efficiency ÷ load Charging = Ah × DoD ÷ (current × efficiency)
Use about 50% DoD for lead-acid and 80–90% for LiFePO4; charging efficiency is about 80–85% and 95%.
What the inputs mean
- Battery capacity
- Rated capacity.
- Voltage
- Battery voltage.
- Load
- Load.
- Depth of discharge
- Share to be used.
- Inverter efficiency
- Inverter efficiency; 100 for DC.
- Charging current
- Charger current.
- Charging efficiency
- Charging efficiency.
Worked example: 100 Ah 12 V, 120 W, 50% DoD, 10 A charger
- Usable energy: 100 × 12 × 0.50 = 600 Wh.
- Runtime: 600 × 0.90 ÷ 120 = 4:30.
- Charging: 50 Ah ÷ (10 × 0.85) = 5:53.
Result: The load runs for 4:30; discharge current 11.11 A.
🔋 Battery Charge and Discharge Calculator
Free, no sign-up; your data stays in your browser.
Open the calculator →Also in this calculator
- Compare: up to three results side by side, with differences in amount and percent
- Download Excel: inputs, result and the table if there is one
- Save: keep the calculation in your own browser only
How to read the result
For preliminary sizing only; a qualified engineer must check the design and protection. Lead-acid capacity falls at high current (Peukert) and in the cold.
Common mistakes
- Using the full capacity.
- Forgetting inverter losses.
- Ignoring the slow end of charging.
Frequently asked questions
Ah or Wh?
Wh compares different voltages: Wh = Ah × V.
What is C?
Current divided by capacity; 0.1C is gentle for lead-acid.
An old battery?
Enter its measured capacity.
The result is not exact or binding and is for information only; it is not an official document and cannot be used in official procedures. Confirm it with the competent authority or a professional before acting; no liability is accepted for losses arising from its use.