Electrical calculators
27 calculators
Ohm's law, power, voltage drop, cable size, transformers, generators and batteries. For preliminary design only; consult a qualified electrician for installation.
- Power TrianglePower triangle: S = P / cos φ (apparent power, kVA). Reactive power: Q = √(S²–P²) ≈ S·sin(arccos PF) kVAr; needed for power factor correction.
- Capacitor Sizing for PF CorrectionCapacitor reactive power for power factor correction: Qc = P·(tan φ₁ − tan φ₂); industrial facilities typically target a power factor of 0.95 or higher.
- Motor Synchronous SpeedSynchronous speed of an induction motor: n_s = 120·f / p; the grid is 50 Hz in Turkey and Europe (60 Hz in North America), and the number of poles must be even (2, 4, 6, 8, 10, 12).
- RLC Resonant FrequencyResonant frequency of a series/parallel RLC circuit: f_r = 1 / (2π√LC); enter L in mH and C in μF. Used in filter and resonant circuit design.
- LV Line Voltage DropPercentage voltage drop on a 3-phase copper low-voltage (LV) line: %e = 100 · P · L / (κ · A · U²); P is active power (W), κ_copper = 56 m/(Ω·mm²). Because active power is used, cos φ cancels out; line reactance is neglected (suitable for short LV lines). Indoor installations typically use limits of 1.5% for lighting and 3% for motor loads.
- Buck (Step-Down) ConverterDuty cycle of an ideal buck (step-down) DC/DC converter: D = Vout / Vin; Vout must be less than Vin. Switching losses are not included.
- Boost (Step-Up) ConverterDuty cycle of an ideal boost (step-up) DC/DC converter: D = 1 − Vin/Vout; Vout must be greater than Vin. Used in solar MPPT and UPS design.
- Total Harmonic Distortion (THD)Total harmonic distortion: THD = √(h2²+h3²+h4²+h5²) / h1 × 100 (up to the 5th harmonic). IEEE 519-2022 limits voltage THD to 8% up to 1 kV and 5% from 1 to 69 kV; current limits depend on the short-circuit ratio.
- Battery RuntimeBattery runtime: t = (Ah × V × η) / P; depth of discharge (DoD), temperature and aging effects are not taken into account.
- Transformer Turns RatioTransformer turns ratio: n = V1/V2 = N1/N2 = I2/I1; n > 1 is a step-down and n < 1 a step-up transformer.
- ImpedanceMagnitude of complex impedance: |Z| = √(R² + X²); XL = 2πfL (inductive), XC = 1/(2πfC) (capacitive); used in power and current calculations.
- Cable Cross-Section SizingMinimum copper cross-section required for a given voltage drop (cos φ = 1, reactance neglected): three-phase A = √3·I·L / (κ·ΔU), single-phase A = 2·I·L / (κ·ΔU); κ = 56 m/(Ω·mm²). Round up to the next standard size (1.5 · 2.5 · 4 · 6 · 10 · 16 · 25 · 35 · 50 · 70 · 95 · 120 mm²) and check the cable's current-carrying capacity separately.
- Three-Phase Motor CurrentFull-load current of a 3-phase induction motor: I = P / (√3 × V × cosφ × η). Used to select motor protection (thermal overload relay, fuse) and cable size.
- Circuit Breaker RatingMinimum breaker/fuse current for 3-phase: I = P·k / (√3·V·cosφ); standard ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 A. Choose the next standard rating above the calculated value.
- Earthing ResistanceCalculates the resistance of a vertically driven earth rod with a simplified formula: R = ρ/(2πL)·ln(4L/d). Soil resistivity varies widely (wet soil 50–200, dry sand 500–1,000 Ω·m); the exact value must be measured. In TT systems the protection condition is R_A × I_Δn ≤ 50 V (IEC 60364-4-41; in Turkey, the Regulation on Earthing in Electrical Installations).
- Power Supply (PSU) WattageCalculates the required PSU wattage from your PC components' power draw, adding about 150 W for the motherboard, drives and fans.
- Ohm's Law (Voltage)Calculates circuit voltage with Ohm's law, V = I × R; enter current (A) and resistance (Ω) to get the result in volts.
- Electrical PowerCalculates electrical power from voltage and current using P = V × I, with the result in watts.
- Series ResistanceCalculates the equivalent resistance of resistors in series, which simply add up: R_total = R1 + R2 + ...
- Parallel ResistanceCalculates the equivalent resistance of three resistors in parallel using 1/R = 1/R1 + 1/R2 + 1/R3; used in circuit analysis.
- Three-Phase Power CalculatorActive, reactive and apparent power, phase angle and daily energy in three-phase or single-phase systems (S = √3·U·I).
- Power Factor Calculatorcos φ and phase angle from active and apparent or reactive power, and the capacitor rating (kVAr) for a target power factor.
- Short-Circuit Current CalculatorEstimates three-phase short-circuit current at the transformer and at the cable end, and the peak current, from rating, uk and cable.
- Transformer Sizing CalculatorRequired transformer kVA, standard size, loading and secondary current from installed power, demand factor, cos φ and spare capacity.
- Generator Sizing CalculatorRequired generator kVA and a common size from loads, demand factor and the start of the largest motor.
- Battery Charge and Discharge CalculatorHow long a battery feeds a load and how long recharging takes, with depth of discharge and efficiency.
- Solar System Sizing CalculatorPanel count, installed power, area, inverter, output and optional battery capacity from daily use and sun hours.