Earthing Resistance
Electrical · 3 inputs · Free
Earthing Resistance
Parameters
What is this tool?
Earthing Resistance applies the basic formulas for electrical installations, circuits and energy. Calculates the resistance of a vertically driven earth rod with a simplified formula: R = ρ/(2πL)·ln(4L/d). Soil resistivity varies widely (wet soil 50–200, dry sand 500–1,000 Ω·m); the exact value must be measured. In TT systems the protection condition is R_A × I_Δn ≤ 50 V (IEC 60364-4-41; in Turkey, the Regulation on Earthing in Electrical Installations).
Inputs: Soil resistivity = 100 Ω·m, Electrode length = 3 m, Electrode diameter = 16 mm
(Soil resistivity ÷ (2 × π × Electrode length)) × ln(4 × Electrode length) ÷ (Electrode diameter ÷ 1000)
Result: 35.1206 Ω
Calculates the resistance of a vertically driven earth rod with a simplified formula: R = ρ/(2πL)·ln(4L/d). Soil resistivity varies widely (wet soil 50–200, dry sand 500–1,000 Ω·m); the exact value must be measured. In TT systems the protection condition is R_A × I_Δn ≤ 50 V (IEC 60364-4-41; in Turkey, the Regulation on Earthing in Electrical Installations).
The result is not exact or binding and is for information only; it is not an official document and cannot be used in official procedures. Confirm it with the competent authority or a professional before acting; no liability is accepted for losses arising from its use.
Last reviewed: · Methodology and sources
How is it calculated?
(Soil resistivity ÷ (2 × π × Electrode length)) × ln(4 × Electrode length) ÷ (Electrode diameter ÷ 1000)
Calculates the resistance of a vertically driven earth rod with a simplified formula: R = ρ/(2πL)·ln(4L/d). Soil resistivity varies widely (wet soil 50–200, dry sand 500–1,000 Ω·m); the exact value must be measured. In TT systems the protection condition is R_A × I_Δn ≤ 50 V (IEC 60364-4-41; in Turkey, the Regulation on Earthing in Electrical Installations).
Inputs
| Value | Unit | Example |
|---|---|---|
| Soil resistivity | Ω·m | 100 |
| Electrode length | m | 3 |
| Electrode diameter | mm | 16 |
What is this tool?
Earthing Resistance applies the basic formulas for electrical installations, circuits and energy. Calculates the resistance of a vertically driven earth rod with a simplified formula: R = ρ/(2πL)·ln(4L/d). Soil resistivity varies widely (wet soil 50–200, dry sand 500–1,000 Ω·m); the exact value must be measured. In TT systems the protection condition is R_A × I_Δn ≤ 50 V (IEC 60364-4-41; in Turkey, the Regulation on Earthing in Electrical Installations).
Worked example
Inputs: Soil resistivity = 100 Ω·m, Electrode length = 3 m, Electrode diameter = 16 mm
Calculation: (Soil resistivity ÷ (2 × π × Electrode length)) × ln(4 × Electrode length) ÷ (Electrode diameter ÷ 1000)
Result: 35.1206 Ω
Common mistakes
- Expecting an exact result from a guessed resistivity instead of a measured one.
- Entering the diameter in cm or m instead of mm.
- Assuming two rods always halve the resistance.
📘 How to Estimate Earthing Resistance of a Ground Rod →
Sources
- IEC 60364-4-41 — Protection against electric shock ↗
- IEC 60364-5-54 — Earthing arrangements and protective conductors ↗
Key terms
Frequently Asked Questions
+Earthing Resistance — how is it calculated?
(Soil resistivity ÷ (2 × π × Electrode length)) × ln(4 × Electrode length) ÷ (Electrode diameter ÷ 1000). Calculates the resistance of a vertically driven earth rod with a simplified formula: R = ρ/(2πL)·ln(4L/d). Soil resistivity varies widely (wet soil 50–200, dry sand 500–1,000 Ω·m); the exact value must be measured. In TT systems the protection condition is R_A × I_Δn ≤ 50 V (IEC 60364-4-41; in Turkey, the Regulation on Earthing in Electrical Installations).
+Which values are required?
Soil resistivity (Ω·m), Electrode length (m), Electrode diameter (mm).
+Can I compare results or export them to Excel?
Yes. After calculating, use “Compare” to put up to three results side by side, “Download Excel” to get a file and “Save” to keep the calculation in your own browser only. No sign-up needed.
+Is my data stored?
No. All calculations run in your browser; the values you enter are never sent to or stored on a server. If you press “Save”, the calculation stays only in your own browser and you can delete it at any time.
+Is it free?
Yes, all tools are free and require no sign-up.
Similar tools
Popular Tools
Free Calculators in One Place
Tax, finance, health, math and more — 500+ tools, all in one place.