Cable Cross-Section Sizing
Electrical · 5 inputs · Free
Cable Cross-Section Sizing
Parameters
What is this tool?
Cable Cross-Section Sizing applies the basic formulas for electrical installations, circuits and energy. Minimum copper cross-section required for a given voltage drop (cos φ = 1, reactance neglected): three-phase A = √3·I·L / (κ·ΔU), single-phase A = 2·I·L / (κ·ΔU); κ = 56 m/(Ω·mm²). Round up to the next standard size (1.5 · 2.5 · 4 · 6 · 10 · 16 · 25 · 35 · 50 · 70 · 95 · 120 mm²) and check the cable's current-carrying capacity separately.
Inputs: Current = 50 A, Line length = 50 m, Allowable voltage drop = 3 %, Line voltage = 400 V, System = Three-phase (400 V)
Result: 6.4436 mm²
Minimum copper cross-section required for a given voltage drop (cos φ = 1, reactance neglected): three-phase A = √3·I·L / (κ·ΔU), single-phase A = 2·I·L / (κ·ΔU); κ = 56 m/(Ω·mm²). Round up to the next standard size (1.5 · 2.5 · 4 · 6 · 10 · 16 · 25 · 35 · 50 · 70 · 95 · 120 mm²) and check the cable's current-carrying capacity separately.
The result is not exact or binding and is for information only; it is not an official document and cannot be used in official procedures. Confirm it with the competent authority or a professional before acting; no liability is accepted for losses arising from its use.
Last reviewed: · Methodology and sources
How is it calculated?
Minimum copper cross-section required for a given voltage drop (cos φ = 1, reactance neglected): three-phase A = √3·I·L / (κ·ΔU), single-phase A = 2·I·L / (κ·ΔU); κ = 56 m/(Ω·mm²). Round up to the next standard size (1.5 · 2.5 · 4 · 6 · 10 · 16 · 25 · 35 · 50 · 70 · 95 · 120 mm²) and check the cable's current-carrying capacity separately.
Inputs
| Value | Unit | Example |
|---|---|---|
| Current | A | 50 |
| Line length | m | 50 |
| Allowable voltage drop | % | 3 |
| Line voltage | V | 400 |
| System | — | Three-phase (400 V) |
What is this tool?
Cable Cross-Section Sizing applies the basic formulas for electrical installations, circuits and energy. Minimum copper cross-section required for a given voltage drop (cos φ = 1, reactance neglected): three-phase A = √3·I·L / (κ·ΔU), single-phase A = 2·I·L / (κ·ΔU); κ = 56 m/(Ω·mm²). Round up to the next standard size (1.5 · 2.5 · 4 · 6 · 10 · 16 · 25 · 35 · 50 · 70 · 95 · 120 mm²) and check the cable's current-carrying capacity separately.
Worked example
Inputs: Current = 50 A, Line length = 50 m, Allowable voltage drop = 3 %, Line voltage = 400 V, System = Three-phase (400 V)
Result: 6.4436 mm²
Common mistakes
- Selecting single-phase but leaving 400 V in the voltage field; enter 230 V for single-phase.
- Not rounding the result up to a standard size, or rounding it down.
- Choosing a size on voltage drop alone without checking current-carrying capacity.
📘 How to Size a Cable by Voltage Drop →
Sources
- IEC 60364-5-52 — Low-voltage electrical installations: wiring systems ↗
- IEC 60228 — Conductors of insulated cables ↗
Key terms
Frequently Asked Questions
+Cable Cross-Section Sizing — how is it calculated?
Minimum copper cross-section required for a given voltage drop (cos φ = 1, reactance neglected): three-phase A = √3·I·L / (κ·ΔU), single-phase A = 2·I·L / (κ·ΔU); κ = 56 m/(Ω·mm²). Round up to the next standard size (1.5 · 2.5 · 4 · 6 · 10 · 16 · 25 · 35 · 50 · 70 · 95 · 120 mm²) and check the cable's current-carrying capacity separately.
+Which values are required?
Current (A), Line length (m), Allowable voltage drop (%), Line voltage (V), System.
+Can I compare results or export them to Excel?
Yes. After calculating, use “Compare” to put up to three results side by side, “Download Excel” to get a file and “Save” to keep the calculation in your own browser only. No sign-up needed.
+Is my data stored?
No. All calculations run in your browser; the values you enter are never sent to or stored on a server. If you press “Save”, the calculation stays only in your own browser and you can delete it at any time.
+Is it free?
Yes, all tools are free and require no sign-up.
Similar tools