Total Harmonic Distortion (THD)
Electrical · 5 inputs · Free
Total Harmonic Distortion (THD)
Parameters
What is this tool?
Total Harmonic Distortion (THD) applies the basic formulas for electrical installations, circuits and energy. Total harmonic distortion: THD = √(h2²+h3²+h4²+h5²) / h1 × 100 (up to the 5th harmonic). IEEE 519-2022 limits voltage THD to 8% up to 1 kV and 5% from 1 to 69 kV; current limits depend on the short-circuit ratio.
Inputs: Fundamental (1st harmonic) RMS = 100 A or V, 2nd harmonic RMS = 5, 3rd harmonic RMS = 10, 4th harmonic RMS = 3, 5th harmonic RMS = 7
(√(2nd harmonic RMS × 2nd harmonic RMS + 3rd harmonic RMS × 3rd harmonic RMS + 4th harmonic RMS × 4th harmonic RMS + 5th harmonic RMS × 5th harmonic RMS) ÷ Fundamental (1st harmonic) RMS) × 100
Result: 13.5277 %
Total harmonic distortion: THD = √(h2²+h3²+h4²+h5²) / h1 × 100 (up to the 5th harmonic). IEEE 519-2022 limits voltage THD to 8% up to 1 kV and 5% from 1 to 69 kV; current limits depend on the short-circuit ratio.
The result is not exact or binding and is for information only; it is not an official document and cannot be used in official procedures. Confirm it with the competent authority or a professional before acting; no liability is accepted for losses arising from its use.
Last reviewed: · Methodology and sources
How is it calculated?
(√(2nd harmonic RMS × 2nd harmonic RMS + 3rd harmonic RMS × 3rd harmonic RMS + 4th harmonic RMS × 4th harmonic RMS + 5th harmonic RMS × 5th harmonic RMS) ÷ Fundamental (1st harmonic) RMS) × 100
Total harmonic distortion: THD = √(h2²+h3²+h4²+h5²) / h1 × 100 (up to the 5th harmonic). IEEE 519-2022 limits voltage THD to 8% up to 1 kV and 5% from 1 to 69 kV; current limits depend on the short-circuit ratio.
Inputs
| Value | Unit | Example |
|---|---|---|
| Fundamental (1st harmonic) RMS | A or V | 100 |
| 2nd harmonic RMS | — | 5 |
| 3rd harmonic RMS | — | 10 |
| 4th harmonic RMS | — | 3 |
| 5th harmonic RMS | — | 7 |
What is this tool?
Total Harmonic Distortion (THD) applies the basic formulas for electrical installations, circuits and energy. Total harmonic distortion: THD = √(h2²+h3²+h4²+h5²) / h1 × 100 (up to the 5th harmonic). IEEE 519-2022 limits voltage THD to 8% up to 1 kV and 5% from 1 to 69 kV; current limits depend on the short-circuit ratio.
Worked example
Inputs: Fundamental (1st harmonic) RMS = 100 A or V, 2nd harmonic RMS = 5, 3rd harmonic RMS = 10, 4th harmonic RMS = 3, 5th harmonic RMS = 7
Calculation: (√(2nd harmonic RMS × 2nd harmonic RMS + 3rd harmonic RMS × 3rd harmonic RMS + 4th harmonic RMS × 4th harmonic RMS + 5th harmonic RMS × 5th harmonic RMS) ÷ Fundamental (1st harmonic) RMS) × 100
Result: 13.5277 %
Common mistakes
- Adding harmonics directly (5 + 10 + 3 + 7 = 25); sum the squares and take the square root.
- Mixing units, for example one harmonic in A and another in %; all values must use the same unit.
- Treating the value up to the 5th harmonic as the full THD; higher-order harmonics are not included.
📘 How to Calculate Total Harmonic Distortion (THD) →
Sources
- IEC 61000 series — Electromagnetic compatibility (EMC) ↗
- IEEE Std 519 — Harmonic control in electric power systems ↗
Key terms
Frequently Asked Questions
+Total Harmonic Distortion (THD) — how is it calculated?
(√(2nd harmonic RMS × 2nd harmonic RMS + 3rd harmonic RMS × 3rd harmonic RMS + 4th harmonic RMS × 4th harmonic RMS + 5th harmonic RMS × 5th harmonic RMS) ÷ Fundamental (1st harmonic) RMS) × 100. Total harmonic distortion: THD = √(h2²+h3²+h4²+h5²) / h1 × 100 (up to the 5th harmonic). IEEE 519-2022 limits voltage THD to 8% up to 1 kV and 5% from 1 to 69 kV; current limits depend on the short-circuit ratio.
+Which values are required?
Fundamental (1st harmonic) RMS (A or V), 2nd harmonic RMS, 3rd harmonic RMS, 4th harmonic RMS, 5th harmonic RMS.
+Can I compare results or export them to Excel?
Yes. After calculating, use “Compare” to put up to three results side by side, “Download Excel” to get a file and “Save” to keep the calculation in your own browser only. No sign-up needed.
+Is my data stored?
No. All calculations run in your browser; the values you enter are never sent to or stored on a server. If you press “Save”, the calculation stays only in your own browser and you can delete it at any time.
+Is it free?
Yes, all tools are free and require no sign-up.
Similar tools
Popular Tools
Free Calculators in One Place
Tax, finance, health, math and more — 500+ tools, all in one place.