LV Line Voltage Drop

Electrical · 4 inputs · Free

📉

LV Line Voltage Drop

4 inputs

Parameters

What is this tool?

LV Line Voltage Drop applies the basic formulas for electrical installations, circuits and energy. Percentage voltage drop on a 3-phase copper low-voltage (LV) line: %e = 100 · P · L / (κ · A · U²); P is active power (W), κ_copper = 56 m/(Ω·mm²). Because active power is used, cos φ cancels out; line reactance is neglected (suitable for short LV lines). Indoor installations typically use limits of 1.5% for lighting and 3% for motor loads.

Inputs: Load power = 10 kW, Line length = 100 m, Conductor cross-section = 25 mm², Line voltage (phase-to-phase) = 400 V

(Load power × 1000 × Line length × 100) ÷ (56 × Conductor cross-section × Line voltage (phase-to-phase) × Line voltage (phase-to-phase))

Result: 0.446 %

📘 Common mistakes · Worked example
Load power (kW)Line length (m)Conductor cross-section (mm²)Line voltage (phase-to-phase) (V)

Percentage voltage drop on a 3-phase copper low-voltage (LV) line: %e = 100 · P · L / (κ · A · U²); P is active power (W), κ_copper = 56 m/(Ω·mm²). Because active power is used, cos φ cancels out; line reactance is neglected (suitable for short LV lines). Indoor installations typically use limits of 1.5% for lighting and 3% for motor loads.

The result is not exact or binding and is for information only; it is not an official document and cannot be used in official procedures. Confirm it with the competent authority or a professional before acting; no liability is accepted for losses arising from its use.

Last reviewed: · Methodology and sources

How is it calculated?

(Load power × 1000 × Line length × 100) ÷ (56 × Conductor cross-section × Line voltage (phase-to-phase) × Line voltage (phase-to-phase))

Percentage voltage drop on a 3-phase copper low-voltage (LV) line: %e = 100 · P · L / (κ · A · U²); P is active power (W), κ_copper = 56 m/(Ω·mm²). Because active power is used, cos φ cancels out; line reactance is neglected (suitable for short LV lines). Indoor installations typically use limits of 1.5% for lighting and 3% for motor loads.

Inputs

ValueUnitExample
Load powerkW10
Line lengthm100
Conductor cross-sectionmm²25
Line voltage (phase-to-phase)V400

What is this tool?

LV Line Voltage Drop applies the basic formulas for electrical installations, circuits and energy. Percentage voltage drop on a 3-phase copper low-voltage (LV) line: %e = 100 · P · L / (κ · A · U²); P is active power (W), κ_copper = 56 m/(Ω·mm²). Because active power is used, cos φ cancels out; line reactance is neglected (suitable for short LV lines). Indoor installations typically use limits of 1.5% for lighting and 3% for motor loads.

Worked example

Inputs: Load power = 10 kW, Line length = 100 m, Conductor cross-section = 25 mm², Line voltage (phase-to-phase) = 400 V

Calculation: (Load power × 1000 × Line length × 100) ÷ (56 × Conductor cross-section × Line voltage (phase-to-phase) × Line voltage (phase-to-phase))

Result: 0.446 %

Common mistakes

  • Entering the go-and-return length; the formula expects the one-way length (with a balanced three-phase load, neutral current is neglected).
  • Using this formula for single-phase circuits; single-phase drop is calculated differently (the Cable Cross-Section tool has a single-phase option).
  • Treating an aluminium cable as copper; the drop is about 1.6 times higher with aluminium.

📘 How to Calculate Voltage Drop on an LV Line: %e = 100·P·L / (κ·A·U²) →

Sources

Key terms

Load power (kW)Line length (m)Conductor cross-section (mm²)Line voltage (phase-to-phase) (V)

Frequently Asked Questions

+LV Line Voltage Drop — how is it calculated?

(Load power × 1000 × Line length × 100) ÷ (56 × Conductor cross-section × Line voltage (phase-to-phase) × Line voltage (phase-to-phase)). Percentage voltage drop on a 3-phase copper low-voltage (LV) line: %e = 100 · P · L / (κ · A · U²); P is active power (W), κ_copper = 56 m/(Ω·mm²). Because active power is used, cos φ cancels out; line reactance is neglected (suitable for short LV lines). Indoor installations typically use limits of 1.5% for lighting and 3% for motor loads.

+Which values are required?

Load power (kW), Line length (m), Conductor cross-section (mm²), Line voltage (phase-to-phase) (V).

+Can I compare results or export them to Excel?

Yes. After calculating, use “Compare” to put up to three results side by side, “Download Excel” to get a file and “Save” to keep the calculation in your own browser only. No sign-up needed.

+Is my data stored?

No. All calculations run in your browser; the values you enter are never sent to or stored on a server. If you press “Save”, the calculation stays only in your own browser and you can delete it at any time.

+Is it free?

Yes, all tools are free and require no sign-up.

Similar tools

Popular Tools

🧮

Free Calculators in One Place

Tax, finance, health, math and more — 500+ tools, all in one place.

Choose your cookie preference to continue

Records the site needs to work (theme, language, favourites) stay in your browser.

This site is free and funded by ads.

With your consent, Google Analytics cookies measure visits and Google AdSense cookies are used to show ads; the data is processed on Google servers abroad.

If you reject, the site works just the same.

Cookie Policy · KVKK notice