LV Line Voltage Drop
Parameters
What is this tool?
LV Line Voltage Drop applies the basic formulas for electrical installations, circuits and energy. Percentage voltage drop on a 3-phase copper low-voltage (LV) line: %e = 100 · P · L / (κ · A · U²); P is active power (W), κ_copper = 56 m/(Ω·mm²). Because active power is used, cos φ cancels out; line reactance is neglected (suitable for short LV lines). Indoor installations typically use limits of 1.5% for lighting and 3% for motor loads.
Inputs: Load power = 10 kW, Line length = 100 m, Conductor cross-section = 25 mm², Line voltage (phase-to-phase) = 400 V
(Load power × 1000 × Line length × 100) ÷ (56 × Conductor cross-section × Line voltage (phase-to-phase) × Line voltage (phase-to-phase))
Result: 0.446 %
Percentage voltage drop on a 3-phase copper low-voltage (LV) line: %e = 100 · P · L / (κ · A · U²); P is active power (W), κ_copper = 56 m/(Ω·mm²). Because active power is used, cos φ cancels out; line reactance is neglected (suitable for short LV lines). Indoor installations typically use limits of 1.5% for lighting and 3% for motor loads.
The result is not exact or binding and is for information only; it is not an official document and cannot be used in official procedures. Confirm it with the competent authority or a professional before acting; no liability is accepted for losses arising from its use.
Last reviewed: · Methodology and sources
How is it calculated?
(Load power × 1000 × Line length × 100) ÷ (56 × Conductor cross-section × Line voltage (phase-to-phase) × Line voltage (phase-to-phase))
Percentage voltage drop on a 3-phase copper low-voltage (LV) line: %e = 100 · P · L / (κ · A · U²); P is active power (W), κ_copper = 56 m/(Ω·mm²). Because active power is used, cos φ cancels out; line reactance is neglected (suitable for short LV lines). Indoor installations typically use limits of 1.5% for lighting and 3% for motor loads.
Inputs
| Value | Unit | Example |
|---|---|---|
| Load power | kW | 10 |
| Line length | m | 100 |
| Conductor cross-section | mm² | 25 |
| Line voltage (phase-to-phase) | V | 400 |
What is this tool?
LV Line Voltage Drop applies the basic formulas for electrical installations, circuits and energy. Percentage voltage drop on a 3-phase copper low-voltage (LV) line: %e = 100 · P · L / (κ · A · U²); P is active power (W), κ_copper = 56 m/(Ω·mm²). Because active power is used, cos φ cancels out; line reactance is neglected (suitable for short LV lines). Indoor installations typically use limits of 1.5% for lighting and 3% for motor loads.
Worked example
Inputs: Load power = 10 kW, Line length = 100 m, Conductor cross-section = 25 mm², Line voltage (phase-to-phase) = 400 V
Calculation: (Load power × 1000 × Line length × 100) ÷ (56 × Conductor cross-section × Line voltage (phase-to-phase) × Line voltage (phase-to-phase))
Result: 0.446 %
Common mistakes
- Entering the go-and-return length; the formula expects the one-way length (with a balanced three-phase load, neutral current is neglected).
- Using this formula for single-phase circuits; single-phase drop is calculated differently (the Cable Cross-Section tool has a single-phase option).
- Treating an aluminium cable as copper; the drop is about 1.6 times higher with aluminium.
📘 How to Calculate Voltage Drop on an LV Line: %e = 100·P·L / (κ·A·U²) →
Sources
- IEC 60364-5-52 — Low-voltage electrical installations: wiring systems ↗
- IEC 60228 — Conductors of insulated cables ↗
Key terms
Frequently Asked Questions
+LV Line Voltage Drop — how is it calculated?
(Load power × 1000 × Line length × 100) ÷ (56 × Conductor cross-section × Line voltage (phase-to-phase) × Line voltage (phase-to-phase)). Percentage voltage drop on a 3-phase copper low-voltage (LV) line: %e = 100 · P · L / (κ · A · U²); P is active power (W), κ_copper = 56 m/(Ω·mm²). Because active power is used, cos φ cancels out; line reactance is neglected (suitable for short LV lines). Indoor installations typically use limits of 1.5% for lighting and 3% for motor loads.
+Which values are required?
Load power (kW), Line length (m), Conductor cross-section (mm²), Line voltage (phase-to-phase) (V).
+Can I compare results or export them to Excel?
Yes. After calculating, use “Compare” to put up to three results side by side, “Download Excel” to get a file and “Save” to keep the calculation in your own browser only. No sign-up needed.
+Is my data stored?
No. All calculations run in your browser; the values you enter are never sent to or stored on a server. If you press “Save”, the calculation stays only in your own browser and you can delete it at any time.
+Is it free?
Yes, all tools are free and require no sign-up.
Similar tools
Popular Tools
Free Calculators in One Place
Tax, finance, health, math and more — 500+ tools, all in one place.