Capacitor Sizing for PF Correction
Electrical · 3 inputs · Free
Capacitor Sizing for PF Correction
Parameters
What is this tool?
Capacitor Sizing for PF Correction applies the basic formulas for electrical installations, circuits and energy. Capacitor reactive power for power factor correction: Qc = P·(tan φ₁ − tan φ₂); industrial facilities typically target a power factor of 0.95 or higher.
Inputs: Active power = 100 kW, Current power factor = 0.75, Target power factor = 0.95
Result: 55.3233 kVAr
Capacitor reactive power for power factor correction: Qc = P·(tan φ₁ − tan φ₂); industrial facilities typically target a power factor of 0.95 or higher.
The result is not exact or binding and is for information only; it is not an official document and cannot be used in official procedures. Confirm it with the competent authority or a professional before acting; no liability is accepted for losses arising from its use.
Last reviewed: · Methodology and sources
How is it calculated?
Capacitor reactive power for power factor correction: Qc = P·(tan φ₁ − tan φ₂); industrial facilities typically target a power factor of 0.95 or higher.
Inputs
| Value | Unit | Example |
|---|---|---|
| Active power | kW | 100 |
| Current power factor | — | 0.75 |
| Target power factor | — | 0.95 |
What is this tool?
Capacitor Sizing for PF Correction applies the basic formulas for electrical installations, circuits and energy. Capacitor reactive power for power factor correction: Qc = P·(tan φ₁ − tan φ₂); industrial facilities typically target a power factor of 0.95 or higher.
Worked example
Inputs: Active power = 100 kW, Current power factor = 0.75, Target power factor = 0.95
Result: 55.3233 kVAr
Common mistakes
- Setting the target below the present value or at exactly 1; full correction to 1 increases the risk of going capacitive at light load.
- Using a single fixed capacitor at a site with variable load.
- Installing unfiltered capacitors where harmonics are present; resonance and capacitor failure can follow.
📘 How to Size Capacitors for Power Factor Correction →
Sources
- IEC 60831 — Shunt power capacitors of the self-healing type for AC systems ↗
- IEEE Std 1036 — Guide for the application of shunt power capacitors ↗
Key terms
Frequently Asked Questions
+Capacitor Sizing for PF Correction — how is it calculated?
Capacitor reactive power for power factor correction: Qc = P·(tan φ₁ − tan φ₂); industrial facilities typically target a power factor of 0.95 or higher.
+Which values are required?
Active power (kW), Current power factor, Target power factor.
+Can I compare results or export them to Excel?
Yes. After calculating, use “Compare” to put up to three results side by side, “Download Excel” to get a file and “Save” to keep the calculation in your own browser only. No sign-up needed.
+Is my data stored?
No. All calculations run in your browser; the values you enter are never sent to or stored on a server. If you press “Save”, the calculation stays only in your own browser and you can delete it at any time.
+Is it free?
Yes, all tools are free and require no sign-up.
Similar tools
Popular Tools
Free Calculators in One Place
Tax, finance, health, math and more — 500+ tools, all in one place.