Three-Phase Motor Current
Electrical · 4 inputs · Free
Three-Phase Motor Current
Parameters
What is this tool?
Three-Phase Motor Current applies the basic formulas for electrical installations, circuits and energy. Full-load current of a 3-phase induction motor: I = P / (√3 × V × cosφ × η). Used to select motor protection (thermal overload relay, fuse) and cable size.
Inputs: Motor power = 15 kW, Line voltage = 400 V, Power factor (cos φ) = 0.85, Efficiency (η) = 92 %
(Motor power × 1000) ÷ (√3 × Line voltage × Power factor (cos φ) × (Efficiency (η) ÷ 100))
Result: 27.6862 A
Full-load current of a 3-phase induction motor: I = P / (√3 × V × cosφ × η). Used to select motor protection (thermal overload relay, fuse) and cable size.
The result is not exact or binding and is for information only; it is not an official document and cannot be used in official procedures. Confirm it with the competent authority or a professional before acting; no liability is accepted for losses arising from its use.
Last reviewed: · Methodology and sources
How is it calculated?
(Motor power × 1000) ÷ (√3 × Line voltage × Power factor (cos φ) × (Efficiency (η) ÷ 100))
Full-load current of a 3-phase induction motor: I = P / (√3 × V × cosφ × η). Used to select motor protection (thermal overload relay, fuse) and cable size.
Inputs
| Value | Unit | Example |
|---|---|---|
| Motor power | kW | 15 |
| Line voltage | V | 400 |
| Power factor (cos φ) | — | 0.85 |
| Efficiency (η) | % | 92 |
What is this tool?
Three-Phase Motor Current applies the basic formulas for electrical installations, circuits and energy. Full-load current of a 3-phase induction motor: I = P / (√3 × V × cosφ × η). Used to select motor protection (thermal overload relay, fuse) and cable size.
Worked example
Inputs: Motor power = 15 kW, Line voltage = 400 V, Power factor (cos φ) = 0.85, Efficiency (η) = 92 %
Calculation: (Motor power × 1000) ÷ (√3 × Line voltage × Power factor (cos φ) × (Efficiency (η) ÷ 100))
Result: 27.6862 A
Common mistakes
- Ignoring efficiency; the nameplate power is shaft power and the motor draws more from the supply.
- Entering the phase-to-neutral voltage (230 V) instead of the line voltage.
- Choosing protection on full-load current alone and ignoring the starting current.
📘 How to Calculate Three-Phase Motor Current →
Sources
- IEC 60034-1 — Rotating electrical machines: rating and performance ↗
- IEC 60034-30-1 — Efficiency classes of line operated AC motors ↗
Key terms
Frequently Asked Questions
+Three-Phase Motor Current — how is it calculated?
(Motor power × 1000) ÷ (√3 × Line voltage × Power factor (cos φ) × (Efficiency (η) ÷ 100)). Full-load current of a 3-phase induction motor: I = P / (√3 × V × cosφ × η). Used to select motor protection (thermal overload relay, fuse) and cable size.
+Which values are required?
Motor power (kW), Line voltage (V), Power factor (cos φ), Efficiency (η) (%).
+Can I compare results or export them to Excel?
Yes. After calculating, use “Compare” to put up to three results side by side, “Download Excel” to get a file and “Save” to keep the calculation in your own browser only. No sign-up needed.
+Is my data stored?
No. All calculations run in your browser; the values you enter are never sent to or stored on a server. If you press “Save”, the calculation stays only in your own browser and you can delete it at any time.
+Is it free?
Yes, all tools are free and require no sign-up.
Similar tools
Popular Tools
Free Calculators in One Place
Tax, finance, health, math and more — 500+ tools, all in one place.