Circuit Breaker Rating

Electrical · 4 inputs · Free

🔧

Circuit Breaker Rating

4 inputs

Parameters

What is this tool?

Circuit Breaker Rating applies the basic formulas for electrical installations, circuits and energy. Minimum breaker/fuse current for 3-phase: I = P·k / (√3·V·cosφ); standard ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 A. Choose the next standard rating above the calculated value.

Inputs: Total load power = 20 kW, Supply voltage = 400 V, Power factor = 0.9, Safety factor = 1.25

(Total load power × 1000 × Safety factor) ÷ (√3 × Supply voltage × Power factor)

Result: 40.0938 A

📘 Common mistakes · Worked example
Total load power (kW)Supply voltage (V)Power factorSafety factor

Minimum breaker/fuse current for 3-phase: I = P·k / (√3·V·cosφ); standard ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 A. Choose the next standard rating above the calculated value.

The result is not exact or binding and is for information only; it is not an official document and cannot be used in official procedures. Confirm it with the competent authority or a professional before acting; no liability is accepted for losses arising from its use.

Last reviewed: · Methodology and sources

How is it calculated?

(Total load power × 1000 × Safety factor) ÷ (√3 × Supply voltage × Power factor)

Minimum breaker/fuse current for 3-phase: I = P·k / (√3·V·cosφ); standard ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 A. Choose the next standard rating above the calculated value.

Inputs

ValueUnitExample
Total load powerkW20
Supply voltageV400
Power factor—0.9
Safety factor—1.25

What is this tool?

Circuit Breaker Rating applies the basic formulas for electrical installations, circuits and energy. Minimum breaker/fuse current for 3-phase: I = P·k / (√3·V·cosφ); standard ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 A. Choose the next standard rating above the calculated value.

Worked example

Inputs: Total load power = 20 kW, Supply voltage = 400 V, Power factor = 0.9, Safety factor = 1.25

Calculation: (Total load power × 1000 × Safety factor) ÷ (√3 × Supply voltage × Power factor)

Result: 40.0938 A

Common mistakes

  • Rounding the result down; always choose the standard rating above the calculated value.
  • Choosing a large device without checking the cable's current-carrying capacity.
  • Using this three-phase formula for a single-phase circuit.

📘 How to Choose a Circuit Breaker Rating for a Three-Phase Load →

Sources

Key terms

Total load power (kW)Supply voltage (V)Power factorSafety factor

Frequently Asked Questions

+Circuit Breaker Rating — how is it calculated?

(Total load power × 1000 × Safety factor) ÷ (√3 × Supply voltage × Power factor). Minimum breaker/fuse current for 3-phase: I = P·k / (√3·V·cosφ); standard ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 A. Choose the next standard rating above the calculated value.

+Which values are required?

Total load power (kW), Supply voltage (V), Power factor, Safety factor.

+Can I compare results or export them to Excel?

Yes. After calculating, use “Compare” to put up to three results side by side, “Download Excel” to get a file and “Save” to keep the calculation in your own browser only. No sign-up needed.

+Is my data stored?

No. All calculations run in your browser; the values you enter are never sent to or stored on a server. If you press “Save”, the calculation stays only in your own browser and you can delete it at any time.

+Is it free?

Yes, all tools are free and require no sign-up.

Similar tools

Popular Tools

🧮

Free Calculators in One Place

Tax, finance, health, math and more — 500+ tools, all in one place.

Choose your cookie preference to continue

Records the site needs to work (theme, language, favourites) stay in your browser.

This site is free and funded by ads.

With your consent, Google Analytics cookies measure visits and Google AdSense cookies are used to show ads; the data is processed on Google servers abroad.

If you reject, the site works just the same.

Cookie Policy · KVKK notice