Circuit Breaker Rating
Electrical · 4 inputs · Free
Circuit Breaker Rating
Parameters
What is this tool?
Circuit Breaker Rating applies the basic formulas for electrical installations, circuits and energy. Minimum breaker/fuse current for 3-phase: I = P·k / (√3·V·cosφ); standard ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 A. Choose the next standard rating above the calculated value.
Inputs: Total load power = 20 kW, Supply voltage = 400 V, Power factor = 0.9, Safety factor = 1.25
(Total load power × 1000 × Safety factor) ÷ (√3 × Supply voltage × Power factor)
Result: 40.0938 A
Minimum breaker/fuse current for 3-phase: I = P·k / (√3·V·cosφ); standard ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 A. Choose the next standard rating above the calculated value.
The result is not exact or binding and is for information only; it is not an official document and cannot be used in official procedures. Confirm it with the competent authority or a professional before acting; no liability is accepted for losses arising from its use.
Last reviewed: · Methodology and sources
How is it calculated?
(Total load power × 1000 × Safety factor) ÷ (√3 × Supply voltage × Power factor)
Minimum breaker/fuse current for 3-phase: I = P·k / (√3·V·cosφ); standard ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 A. Choose the next standard rating above the calculated value.
Inputs
| Value | Unit | Example |
|---|---|---|
| Total load power | kW | 20 |
| Supply voltage | V | 400 |
| Power factor | — | 0.9 |
| Safety factor | — | 1.25 |
What is this tool?
Circuit Breaker Rating applies the basic formulas for electrical installations, circuits and energy. Minimum breaker/fuse current for 3-phase: I = P·k / (√3·V·cosφ); standard ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 A. Choose the next standard rating above the calculated value.
Worked example
Inputs: Total load power = 20 kW, Supply voltage = 400 V, Power factor = 0.9, Safety factor = 1.25
Calculation: (Total load power × 1000 × Safety factor) ÷ (√3 × Supply voltage × Power factor)
Result: 40.0938 A
Common mistakes
- Rounding the result down; always choose the standard rating above the calculated value.
- Choosing a large device without checking the cable's current-carrying capacity.
- Using this three-phase formula for a single-phase circuit.
📘 How to Choose a Circuit Breaker Rating for a Three-Phase Load →
Sources
- IEC 60364-4-43 — Protection against overcurrent ↗
- IEC 60898-1 — Circuit-breakers for household and similar installations ↗
Key terms
Frequently Asked Questions
+Circuit Breaker Rating — how is it calculated?
(Total load power × 1000 × Safety factor) ÷ (√3 × Supply voltage × Power factor). Minimum breaker/fuse current for 3-phase: I = P·k / (√3·V·cosφ); standard ratings: 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100 A. Choose the next standard rating above the calculated value.
+Which values are required?
Total load power (kW), Supply voltage (V), Power factor, Safety factor.
+Can I compare results or export them to Excel?
Yes. After calculating, use “Compare” to put up to three results side by side, “Download Excel” to get a file and “Save” to keep the calculation in your own browser only. No sign-up needed.
+Is my data stored?
No. All calculations run in your browser; the values you enter are never sent to or stored on a server. If you press “Save”, the calculation stays only in your own browser and you can delete it at any time.
+Is it free?
Yes, all tools are free and require no sign-up.
Similar tools
Popular Tools
Free Calculators in One Place
Tax, finance, health, math and more — 500+ tools, all in one place.