Power Factor (cos φ) and Correction
Last updated: · 2 min read
Power factor shows how much of the apparent power does useful work. A low value raises current and can add reactive charges. The tool finds cos φ from active and apparent or reactive power and the capacitor needed for a target.
Formula
cos φ = P ÷ S Q = √(S² − P²) Qc = Q − P × tan(arccos target)
The capacitor supplies reactive power above the target; active power does not change.
What the inputs mean
- Known value
- Whether the second value is apparent or reactive.
- Active power
- Active power (kW).
- Value
- The value itself.
- Target power factor
- Target cos φ.
Worked example: 80 kW active, 100 kVA apparent, target 0.98
- cos φ: 80 ÷ 100 = 0.8.
- Reactive power: √(100² − 80²) = 60 kVAr.
- Capacitor for the target: 43.76 kVAr.
Result: After correction apparent power falls to 81.63 kVA.
Also in this calculator
- Compare: up to three results side by side, with differences in amount and percent
- Chart: how the result moves when one value changes
- Download Excel: inputs, result and the table if there is one
- Save: keep the calculation in your own browser only
How to read the result
For preliminary sizing only; a qualified engineer must check the design and protection. Overcorrection leads to a capacitive power factor.
Common mistakes
- Aiming too close to 1.
- Using plain capacitors with harmonics.
- Measuring a single moment instead of the average.
Frequently asked questions
What is the limit for reactive charges?
It depends on your grid operator.
Do inverters matter?
Yes, they affect power factor and harmonics.
How are steps chosen?
By the variation of the load.