How to Size a Generator: Motor Starting

Last updated: · 2 min read

Sizing a generator from the total load alone lets the voltage collapse when a large motor starts. The tool computes the continuous load with spare and the starting moment with a factor, takes the larger and rounds to a common size.

Formula

Continuous = P × k ÷ cos φ
Start = (P × k − motor + motor × factor) ÷ cos φ
S = max(continuous × (1 + spare); start)

The factor depends on the starter: direct 2.5–3, star-delta 1.5–2, soft starter or drive 1.2–1.5.

What the inputs mean

Total load
Total load.
Demand factor
Demand factor.
Power factor
Rated power factor, usually 0.8.
Largest motor
Largest motor.
Starting factor
Starting factor.
Spare capacity
Spare on continuous load.

Worked example: 60 kW, demand 0.8, 11 kW motor, factor 2.5

  1. Continuous: 48 ÷ 0.8 = 60 kVA.
  2. Start: (48 − 11 + 27.5) ÷ 0.8 = 80.63 kVA.
  3. Required 80.63 kVA; common size 100 kVA.

Result: A 100 kVA set delivers about 64.5 kW.

🔌 Generator Sizing Calculator

Free, no sign-up; your data stays in your browser.

Open the calculator →

Also in this calculator

  • Compare: up to three results side by side, with differences in amount and percent
  • Chart: how the result moves when one value changes
  • Download Excel: inputs, result and the table if there is one
  • Save: keep the calculation in your own browser only

How to read the result

For preliminary sizing only; a qualified engineer must check the design and protection. Use the maker's curves for altitude, temperature and UPS loads.

Common mistakes

  • Ignoring motor starts.
  • Mixing standby and prime ratings.
  • Mixing kVA and kW.

Frequently asked questions

Prime versus standby?

Prime is for continuous variable load, standby for outages.

UPS loads?

Often 1.5–2 times their rating because of harmonics.

Fuel use?

About 0.25–0.3 litres of diesel per kWh.

The result is not exact or binding and is for information only; it is not an official document and cannot be used in official procedures. Confirm it with the competent authority or a professional before acting; no liability is accepted for losses arising from its use.

Sources

Choose your cookie preference to continue

Records the site needs to work (theme, language, favourites) stay in your browser.

This site is free and funded by ads.

With your consent, Google Analytics cookies measure visits and Google AdSense cookies are used to show ads; the data is processed on Google servers abroad.

If you reject, the site works just the same.

Cookie Policy · KVKK notice