Short-Circuit Current: Transformer and Cable

Last updated: · 2 min read

To choose a breaker you need the largest short-circuit current at that point. The tool estimates the current at the transformer from its rating and uk and at the cable end from length and section, plus the peak value.

Formula

Zt = uk × U² ÷ S
Ik = U ÷ (√3 × √(R² + (Xt + Xk)²))
ip = κ × √2 × Ik

The grid is taken as infinite, the transformer as purely inductive, cable reactance as 0.08 mΩ/m and voltage factor 1.

What the inputs mean

Transformer rating
Transformer rating.
Impedance voltage (uk)
Impedance voltage on the nameplate.
Secondary voltage
Secondary line voltage.
Cable length
Cable length to the point.
Cable section (per phase)
Section per phase.
Conductor
Copper or aluminium.

Worked example: 630 kVA, uk 4%, 400 V, 20 m of 150 mm² copper

  1. Transformer impedance 10.16 mΩ; at the terminals 22.73 kA.
  2. Cable resistance 2.47 mΩ.
  3. At the cable end 19.22 kA; peak 41.92 kA.

Result: The breaker here needs a breaking capacity of at least 19.22 kA.

🧨 Short-Circuit Current Calculator

Free, no sign-up; your data stays in your browser.

Open the calculator →

Also in this calculator

  • Compare: up to three results side by side, with differences in amount and percent
  • Chart: how the result moves when one value changes
  • Download Excel: inputs, result and the table if there is one
  • Save: keep the calculation in your own browser only

How to read the result

For preliminary sizing only; a qualified engineer must check the design and protection. Motor contribution and hot cable resistance are ignored; use IEC 60909 for a full study.

Common mistakes

  • Entering a return length.
  • Typing uk as a decimal.
  • Treating the result as a trip setting.

Frequently asked questions

Minimum short-circuit current?

That needs phase-neutral impedance; this gives the maximum.

Unknown grid power?

An infinite grid gives the largest current.

Parallel cables?

Multiply the section.

The result is not exact or binding and is for information only; it is not an official document and cannot be used in official procedures. Confirm it with the competent authority or a professional before acting; no liability is accepted for losses arising from its use.

Sources

Choose your cookie preference to continue

Records the site needs to work (theme, language, favourites) stay in your browser.

This site is free and funded by ads.

With your consent, Google Analytics cookies measure visits and Google AdSense cookies are used to show ads; the data is processed on Google servers abroad.

If you reject, the site works just the same.

Cookie Policy · KVKK notice