Three-Phase Power: kW, kVA and kVAr
Last updated: · 2 min read
To find the real power of a three-phase machine from its current you need both voltage and power factor. The tool gives active (kW), reactive (kVAr) and apparent (kVA) power, phase angle and daily energy; it also handles single-phase circuits.
Formula
Three-phase: S = √3 × U × I ÷ 1000 · Single-phase: S = U × I ÷ 1000 P = S × cos φ Q = S × √(1 − cos² φ)
In three-phase U is the line voltage (400 V); in single-phase the phase-neutral voltage (230 V). A balanced load is assumed.
What the inputs mean
- System
- Number of phases.
- Voltage (line / phase-neutral)
- Line voltage, or phase-neutral for single-phase.
- Current
- Line current.
- Power factor (cos φ)
- Typically 0.75–0.92 for motors.
Worked example: 400 V, 25 A, cos φ 0.85
- Apparent power: √3 × 400 × 25 ÷ 1000 = 17.32 kVA.
- Active power: 17.32 × 0.85 = 14.72 kW.
- Reactive power 9.12 kVAr; phase angle 31.79 °.
Result: The machine draws 14.72 kW; running 24 hours it uses 353.34 kWh.
⚡ Three-Phase Power Calculator
Free, no sign-up; your data stays in your browser.
Open the calculator →Also in this calculator
- Compare: up to three results side by side, with differences in amount and percent
- Chart: how the result moves when one value changes
- Download Excel: inputs, result and the table if there is one
- Save: keep the calculation in your own browser only
How to read the result
For preliminary sizing only; a qualified engineer must check the design and protection.
Common mistakes
- Forgetting √3 in three-phase.
- Using phase-neutral voltage in the three-phase formula.
- Treating kVA and kW as equal.
Frequently asked questions
Do I pay for kVA or kW?
For energy in kWh; reactive energy may be billed above a limit.