Steam Condensate Load
Engineering · 2 inputs · Free
Steam Condensate Load
Parameters
What is this tool?
Steam Condensate Load applies the core formulas of engineering and physics. Calculates the amount of steam condensed for a given heat load: ṁ = Q / h_fg. Saturation temperature comes from the Antoine equation, and latent heat h_fg from a curve fitted to steam tables (±0.5% between 100 and 250 °C). Used for sizing steam traps.
Inputs: Heat load = 100 kW, Steam pressure (absolute) = 300 kPa
Result: 166.0497 kg/h
Calculates the amount of steam condensed for a given heat load: ṁ = Q / h_fg. Saturation temperature comes from the Antoine equation, and latent heat h_fg from a curve fitted to steam tables (±0.5% between 100 and 250 °C). Used for sizing steam traps.
The result is not exact or binding and is for information only; it is not an official document and cannot be used in official procedures. Confirm it with the competent authority or a professional before acting; no liability is accepted for losses arising from its use.
Last reviewed: · Methodology and sources
How is it calculated?
Calculates the amount of steam condensed for a given heat load: ṁ = Q / h_fg. Saturation temperature comes from the Antoine equation, and latent heat h_fg from a curve fitted to steam tables (±0.5% between 100 and 250 °C). Used for sizing steam traps.
Inputs
| Value | Unit | Example |
|---|---|---|
| Heat load | kW | 100 |
| Steam pressure (absolute) | kPa | 300 |
What is this tool?
Steam Condensate Load applies the core formulas of engineering and physics. Calculates the amount of steam condensed for a given heat load: ṁ = Q / h_fg. Saturation temperature comes from the Antoine equation, and latent heat h_fg from a curve fitted to steam tables (±0.5% between 100 and 250 °C). Used for sizing steam traps.
Worked example
Inputs: Heat load = 100 kW, Steam pressure (absolute) = 300 kPa
Result: 166.0497 kg/h
Common mistakes
- Entering gauge pressure instead of absolute pressure; the saturation temperature and h_fg come out wrong.
- Entering the heat load in kWh, BTU/h or kcal/h instead of kW; 100,000 kcal/h ≈ 116.3 kW and 1,000,000 BTU/h ≈ 293 kW.
- Sizing traps for the steady load only; start-up loads are much higher.
- Assuming measured condensate includes sensible cooling; the formula only counts latent heat.
📘 How to Calculate Steam Condensate Load: ṁ = Q / h_fg →
Sources
- IAPWS — Industrial Formulation 1997 (IAPWS-IF97) ↗
- NIST Chemistry WebBook — Thermophysical properties of water ↗
Key terms
Frequently Asked Questions
+Steam Condensate Load — how is it calculated?
Calculates the amount of steam condensed for a given heat load: ṁ = Q / h_fg. Saturation temperature comes from the Antoine equation, and latent heat h_fg from a curve fitted to steam tables (±0.5% between 100 and 250 °C). Used for sizing steam traps.
+Which values are required?
Heat load (kW), Steam pressure (absolute) (kPa).
+What should “Heat load” be to get 207.5621 kg/h?
With the other example values unchanged, entering 125 kW for “Heat load” gives 207.5621 kg/h. For your own target, calculate first, then press “Solve backwards” and type the result you want.
+Can I compare results or export them to Excel?
Yes. After calculating, use “Compare” to put up to three results side by side, “Download Excel” to get a file and “Save” to keep the calculation in your own browser only. No sign-up needed.
+Is my data stored?
No. All calculations run in your browser; the values you enter are never sent to or stored on a server. If you press “Save”, the calculation stays only in your own browser and you can delete it at any time.
+Is it free?
Yes, all tools are free and require no sign-up.